Совершенствование методов контроля изоляции электрооборудования высокого напряжения на основе высокочастотного зондирования
Иванов Александр Викторович, Рыбаков Леонид Максимович · Вестник Чувашского университета · 2015
The article regards the techniques currently used to monitor power transformers insulation. It demonstrates typical drawbacks common for all methods: the existing methods detect only defects distributed throughout the power transformer and do not reveal the concentrated (local) defects that symbolize the beginning of degradation of the «solid dielectric oil» insulation system. Most of the employed methods are sensitive to the state of oil poured into the transformer, making it difficult to detect defects in solid insulation. Monitoring insulation on working electric installations by existing methods is hindered by the influence of external electromagnetic fields generated by operating high-voltage equipment located near the transformer being monitored. A new method is proposed to monitor insulation, which is based on high-frequency sensing. In terms of insulation control, the circuit of the power transformer winding varies corresponding to applied voltage frequency change from 0 to ∞ taking into account active resistance, inductivity and capacity. We designed a device for monitoring the state of insulation which allows to evaluate the distributed defects of the coil as well as the defects concentrated in the coils layers.