Расчет несимметрии напряжений СЭС
Дулепов Дмитрий Евгеньевич, Тюндина Татьяна Евгеньевна · Вестник НГИЭИ · 2015
The article discusses the indicators of quality of electric energy (CE) for parameters characterizing the voltage unbalance in three-phase systems. The voltage unbalance is a phenomenon in which the amplitude of the phase voltages and/or the angles between them are not equal. Discusses the causes and consequences of occurrence of voltage unbalance SES. The main causes of voltage unbalance in three-phase power systems. In the main part of the article describes ways of reducing and basic methods of calculating voltage unbalance. Describes in detail a method of reducing the unbalance by using cross-reactive power compensation. As sources of reactive power consumers and power distribution systems for agricultural purposes (ESSN) recommended installation of the transverse capacitive compensation (KU) as a rule, complete and disable. The example of calculation of voltage unbalance, it is produced by the equivalent circuit network of the reverse sequence. In conclusion, noted that to date, the voltage unbalance is an important issue and requires an immediate solution, as rural distribution networks are characterized by considerable asymmetry of currents and voltages. This is one of the main reasons for the decline of power quality and increase of power losses in the network. The values of indicators of quality of electric energy to more than 5 times higher than established by GOST values, and the increase of power losses ranging from 40 to 130 %.
Cited by 0 works.