Показатели надежности схем городской электрической сети для питания потребителей второй и третьей категорий

М. А. Короткевич, А. Л. Старжинский · Electronic scientific archive of UrFU (Ural Federal University) · 2012

The paper considers two schemes of the urban distributive electric network for supply of the second and third category consumers for whom indicators of reliability have been determined. As for a network scheme of the 2 nd category it has been determined that while installing low-oil and vacuum switches at a distributive point the most remote transformer substation has the highest non-availability  factor which is higher of the corresponding non-availability  factor of the nearest transformer substation by 1,21–1,23 fold  accordingly. As for a network scheme of the 3 rd category consumers it has been obtained the data that reliability of consumers receiving supply from bus-bars of transformer substations with 0,38 kW voltage changes  significantly (by 1,2–1,9-fold) while changing a breakpoint of the network with 10 kW voltage.

Cited by 0 works. Open-access PDF

Authors