Визуализация мест локального перегрева изоляции кабелей

Леонов Андрей Петрович, Veronika Bolgova · Интернет-журнал Науковедение · 2014

A significant number of electrical equipment failures occurs due to latent defects and weakened insulation. In the majority of cases it’s caused by the overheating impact. The risk of cable insulation overheating consists in the thermal aging acceleration, the electrical and mechanical properties deterioration; it leads to service life period reducing and can be a cause of fire hazards. Currently, the detection of inadmissible insulation overheating places is difficult even in areas of exposed wiring and electric service panel. This paper presents a new technical solution elaboration providing a simple and illustrative method for the electrical insulation critical temperature rise control. Developed by the authors cable product design using thermoindicators is described. This cable product design provides the insulation critical overheating visualization and the weakened cable or wire timely replacement for prevent an emergency situation and electrical equipment failure. The special thermoindicators additives inserting in the polymeric insulation outer layer is proposed by the authors., otherwise stated, it allows to turning into a temperature sensor the entire test surface. The performed thermal design taking into account the current loads confirms the reality of achieving marked temperatures during the cable products operation. It''s mentioned, proposed design implementation doesn’t require the significant changes of technological process existing on most cable factories producing plastic insulated cables. Authors developed design is protected by patent of Russian Federation.

Cited by 0 works.

Authors