Моделирование и эксергетический анализ одноступенчатой аммиачной экспериментальной холодильной машины
Larisa Vasilievna Galimova, Камнев Антон Анатольевич, Лазаренко Олег Олегович et al. · OIL AND GAS TECHNOLOGIES AND ENVIRONMENTAL SAFETY · 2008
The efficiency estimation of refrigeration machine units is determined on the basis of exergy efficiency definition which shows a degree of plant approach to an ideal. The purpose of matter is the analysis of the cycle of experimental refrigeration machine in operating conditions. For achievement of this aim the parameters of the working refrigeration machine have been taken, the incorporated technique of thermal design and exergy losses definition in elements of the refrigeration machine is developed and according to it calculations are carried out, the block diagram and the program code for thermal design, exergy losses definition in elements of the machine and in the cycle as a whole is developed, numerical experiment is carried out and adequacy of the program code is established, schemes of exergy flows and losses in elements of the circuit are constructed, the analysis of the received dependences is made and qualitative exergy reasons are given. Exergy analysis of the experimental one-stage ammonia refrigeration machine in conditions of low temperature of the cooling water, providing approximation to adiabatic compression, allows to define limiting values of losses in piston compressors. The analysis of the condenser work helps to make the conclusion about impurity heat exchanging surface. The received values of losses in elements of experimental plant can be used in the analysis of real refrigeration machine
Cited by 0 works.