Исследование влияния температуры на параметры напряжения саморазряда и возвратного напряжения, определяющие остаточный ресурс трансформаторов
Матвеева Елена Валерьевна, Козяков Дмитрий Владимирович, Семенов Дмитрий Александрович · Вестник НГИЭИ · 2015
Using a previously developed device to measure the insulation on modern element base with the use of the ADC connected to the computer through a USB port that allows the use to control the diagnostic process portable Notebook-type PC, a study was conducted of the effect of temperature on the diagnostic parameters voltage self-discharge and reverse voltage, determining the remaining life of transformers. For testing we have chosen a uniform method of measurement of voltage-discharge and reverse voltage. On the basis of earlier studies concluded that it is necessary to apply a test voltage to the HV winding and grounded to the coil LV. The dependences of the voltage-discharge time at different temperatures of the transformer tank, the dependence of the intensities of the exponential components of the voltage-discharge isolation from the temperature of the tank and windings, as well as the values and dependencies reverse voltage at different temperatures of the transformer tank. The study determined the effect of temperature on the measured parameters voltage and discharge return voltage. On the basis of obtained experimental data the proposed empirical relations with correction for temperature to determine the residual life of isolation with regard to the changes in temperature of the transformer for measurements in the range from +10 to +40 oC.
Cited by 0 works.