열전달 촉진관에서의 저온 비등열전달 실험 및 이력현상 특성

박종익, 윤필현, 정진희 et al. · 대한설비공학회 학술발표대회논문집 · 2002

The objectives of this paper are to study the boiling characteristics, to elucidate the onset criterion of the hysteresis at low temperature (about -90℃) on enhanced surfaces, and to provide a guideline for optimum operation conditions at low temperature boiling for practical refrigeration applications. Working fluid is R134a, and four Turbo-B tubes are used to enhance the heat transfer performance. Initial boiling conditions (cases 1, 2 and 3), refrigerant temperature, and inlet temperature of the chilled water are considered as the key parameters during the experiments. The results show that the overall heat transfer coefficient for the low temperature boiling is about 1/2 times lower than that for normal condition (5℃) due to the boiling hysteresis at low temperature. It is also concluded that the abnormal operation can be avoided during the low temperature boiling if the refrigeration system is started with LMTD larger than 3.4℃ at initial stage and larger than 1.0℃ at normal stage.

Cited by 0 works.