전압강하에 따른 화재비상경보 설비음의 변동특성

신훈, 백건종, 송민정 et al. · 한국건축친환경설비학회 학술발표대회 논문집 · 2009

In this study, effects of voltage dropping due to distance increasement between receiver and terminal circuit were examined and especially effects on fire alarm sound pressure level in receiving point were identified according to plan types. Following are results. (1) With the voltage dropping increases, the fire alarm sound pressure level decreases. When voltage dropped by -20%, alarm bell sound decreases by -3.5㏈ and siren does by -2.3㏈. (2) In the experiments of sound pressure level variation caused by voltage dropping and plan types, the sound pressure level reduction in corridor type plan is bigger than that of stairway type plan's. The attenuated sound pressure level due to voltage dropping could not be heard in lecture room and so, this problem should be considered.