[論文] 응축폐열을 이용한 건조 및 온수장치에 관한 연구

박노현, 고하영, 정진웅 et al. · 설비저널 · 1986

In the normal Refrigeration process, the condensation heat of refrigerant has not been used because of its low-temperature waste heat. To recover the condensation waste heat of R-12 refrigerator, a drying and hot water system was designed and experimented. The results obtained were summarized as follows: 1. As the temperature a tmosphere was increased, the temperature of discharge gas of compressor was increased. And the temperature was 80-84℃ for air condensing type and was 68-71℃ for water condensing type during summer. 2. The condensation waste heat could be obtained up to 50-55°C of drying heat-source and Hot water in summer. In this case, recovered rate was about 73%. And the more temperature of drying Heat-source and Hot water were increased, the more a recovered rate were decreased. 3. When comparing drying characteristics of Agro-products in dryer of waste heat utilization and Hot air, there was no quality difference in products. But drying time of the former was 3 Hours longer than the latter. 4. The condensation waste heat of compressor' could be applied into the drying of marine products, the pre drying of agro-products and making hot water. And showed high possibility of the waste heat using in low-temperature storage.