수직밀폐형 지중 열교환기 형태에 따른 열효율 평가
윤석, 고규현, 이승래 et al. · 2013
This research presents an experimental study of heat exchange rate of U, W, 2U and coil type ground heat exchangers (GHEs) measured by thermal performance tests(TPTs). The four type sof GHEs were installed in a partially saturated dredged soil de posit of Incheon International Airport area. Thermal response test(TRTs) were conducted for U, W and 2U type GHEs to deduce the ground thermal conductivity. Besides, TPTs were also conducted for U, W, 2U and coil type GHEs to evaluate heat exchanger rates under 100-hr continuous and 8-hr intermittent operation conditions for five days. Coil shaped GHE showed about twice higher thermal performance than others GHEs. Furthermore, intermittent operation condition showed 30~40% higher heat exchange rates than continuous operation condition.
Cited by 0 works.
Authors
References
- Energy foundations and other thermo-active ground structures
- Comparison of the thermal performance of double U-pipe borehole heat exchangers measured in situ
- A new model and analytical solutions for borehole and pile ground heat exchangers
- Heat transfer analysis of pile geothermal heat exchangers with spiral coils
- Evaluation of thermal response and performance of PHC energy pile: Field experiments and numerical simulation
- The Effects of the Installation Conditions of Ground Loop Heat Exchanger to the Thermal Conductivity and Borehole Resistance
- DSRC 자료를 이용한 고속도로 단기 통행시간 예측
- Evaluation of Effective Thermal Conductivity and Thermal Resistance in Ground Heat Exchanger Boreholes
- Evaluation of Ground Thermal Conductivity by Performing In-Situ Thermal Response test (TRT) and CFD Back-Analysis
- Thermal Conductivity Estimation of Soils Using Coil Shaped Ground Heat Exchanger