전류변성기 비교기와 정밀션트저항을 이용한 전류변성기용 부담의 평가기술
鄭在甲, 李相和, 姜銓洪 et al. · 전기학회논문지 C · 2006
Both ratio error and phase angle error in current transformer(CT) depend critically on values of CT burden. Thus, precise measurement of CT burden is very important for the evaluation of CT. A method for the measurement of CT burden has been developed by employing the portable shunt precise resistor with negligible AC-DC resistance difference less than 10 -5 . The burden valuetvalue and power factor) can be calculated from resistance and reactance obtained by measuring the change of ratio error and phase angle error caused by the change of shunt resistor. The uncertainty for the method is evaluated and found to be about 2 %.
Cited by 0 works.