유턴 흐름을 갖는 차량공조용 플레이트형 증발기의 전열특성에 관한 연구
강정길, 김종수 · 설비공학논문집 · 1999
The evaporation heat transfer and pressure drop characteristics for HFC-134a in flat plate type heat exchangers with enhanced beads were experimentally investigated. Three plate type evaporators with different geometric condition of U-turn area were tested. Mass fluxes were tested over the range of 83 ㎏/㎡s to 166 ㎏/㎡s, and heat fluxes were varied from 4 ㎾/㎡ to 12 ㎾/㎡. Evaporation temperature was 5℃ with inlet qualities of 0.1 to 1.0. There was no notable difference in the heat transfer coefficient by geometric variation of U-turn area, but the third plate with cross-ribbed channel at U-turn area was better than others in the evaluation using volume goodness factor comparison. Also, the mixtures of HFC-134a and PAG oil was tested to determine oil effects on heat transfer and pressure drop. As oil concentration was increased, heat transfer coefficient was increased by 22-48% up to the 3 wt.%, but decreased by 14-22% at the 4 wt.%. The pressure drop was increased by the maximum of 100% as oil concentration was increased.