히트파이프 열교환기의 응축부 수분무시 엔탈피효율 산정에 관한 실험적 연구
최상곤, 홍진관, 양권옥 et al. · 대한설비공학회 학술발표대회논문집 · 2001
Experimental study for performance improvement of heat pipe heat exchanger(HPHE) was carried out. The Performance test was conducted by varying tilt angle, air velocity, fin type and number of rows in the case of with and without water spray in condenser section of HPHE. Experimental results show that the enthalphy efficiency of HPHE in the case of water spray is increased with maximum 20% comparing with the case of without water spray in condenser section. The experimental results will be useful in a variety of applications, especially in design and manufacturing of a high-efficiency energy recovery systems.
Cited by 0 works.