개별공조시스템에 의한 기류분포 및 환기특성
최선호, 한화택, 정광섭 et al. · 대한설비공학회 학술발표대회논문집 · 2000
This paper investigates ventilation characteristics and room airflow distributions in a workstation area by a personal air-conditioning system for heating conditions. Tracer gas experiments are performed to measure local supply index and room mean ventilation effectiveness, and PIV experiments are performed to obtain quantitative velocity vectors in the workstation area. As a result, the local supply index in the workstation area is found to be increased by a PEM (Personal Environmental Module) system compared to the case of UFAC (Under-floor Air-Conditioning) system, while overall room ventilation effectiveness remains the same. Flow visualization results indicate that the horizontal warm supply air from PEM moves upward over the breathing zone in the workstation area because of buoyancy force. The local supply index at the occupant breathing zone can be improved by adjusting the angle of the PEM diffuser grille downward.