송풍-역풍 겸용 축류팬 피치각에서 역풍시 효율저하 원인에 관한 연구
김화영, 허진혁, 문승재 et al. · 대한설비공학회 하계학술발표회 논문집 · 2009
In this study, the numerical study has carried out to analyze the factors of the efficiency decrease at backward flow situation in an axial fan with adjustable blades. The analysis is carried out the pitch angle 36˚ on the forward flow and the pitch angle -26˚ on the backward flow. The numerical results show that the air flow rates of the pitch angle 36˚and -26˚ are respectively calculated to 285 CMM and 212 CMM. The results are similar to the experimental results carried out by Chang, and have made the maximum error of 10.6% when compared with the experimental results. The important reason of the fan efficiency decrease is that axial fan used for this study was designed to use for the forward flow. As the results, the pitch angle -26˚ has occurred the recirculation around the impeller blade, impeller cover and stator.
Cited by 0 works.