지하 수처리시설 유지관리층 환기설비의 성능평가
강한기, 이재헌 · 대한설비공학회 동계학술발표회 논문집 · 2007
In this paper, the ventilation efficiencies of an underground sewage disposal plant were investigated for ventilating system without fan, ventilating system with eleven cross flow fans and ventilating system with sixteen cross flow fans by numerical method. It has been found that the air change effectiveness of the system without fan was predicted 0.44. It means that an additional ventilating equipment is needed to maintain good indoor air quality. For the ventilating system with sixteen cross flow fans, the air change effectiveness was predicted 0.55. The air change effectiveness of the ventilating system with eleven cross flow fans was predicted 0.51. It is known that the air change effectiveness above 0.5 is enough to eliminate pollutant and bad smell in the indoor. Therefore, it is recommended to select the ventilating system with eleven cross flow fans for the underground sewage disposal plant in an economic point of view.