전류변성기 비교 측정 장치의 비오차 및 위상각 오차의 직선성 현장 평가기술
鄭在甲, Quan Yuan, 李相和 et al. · 전기학회논문지 C · 2006
A method for evaluation of the linearity of both the ratio error and phase angle error in the current transformer(CT) comparison measurement equipment has been developed by employing the standard resistors with negligible AC-DC resistance difference less than 10??. The non-reactive standard resistors for the linearity check of the system are used as the external burden connected with the secondary of CT under test. These burdens consist of nine standard resistors, with the nominal resistance of 0.01 Ω, 0.1 Ω, 0.2 Ω, 0.4 Ω, 0.6 Ω, 1 Ω, 2 Ω, 4 Ω, and 10 Ω. For linearity check, the developed method has been applied in the CT comparison measurement equipment belonging to the industry.