소방 배관 동파방지용 열선의 위치 선정을 위한 비정상 열전달 수치해석
이동욱, 최형권 · 대한기계학회 춘추학술대회 · 2014
In this paper, the unsteady incompressible Navier-Stokes equation coupled with energy equation was solved in order to find a cold region and investigate a water temperature profile inside pipe for various locations of electrical heat trace. A commercial code(ANSYS-FLUENT) was used for the present simulations. Locations of heat trace were 6 oclock, 12 oclock, 3 oclock and 4 and half oclock. It was found that the minimum and average temperatures of water are different for each case because the buoyancy effect varies with the location of heat trace. Further, it was also found that water moved down when it was heating up from 0°C to 4°C with the 12 oclock trace since water density is highest at 4°C.
Cited by 2 works.