압축기 가변에 따른 지열원 물대물 열펌프 유닛의 충전량 변화에 따른 성능 특성

조찬용, 김남태, 이대희 et al. · 대한설비공학회 학술발표대회논문집 · 2010

The objective of this study is to investigate the effects of the refrigerant charge amount on the performance of a water-to-water ground source heat pump at different compressor speeds. The water-to-water ground source heat pump was tested by varying refrigerant charge amount from -30% to 10% of full charge and changing compressor speed from 30Hz to 75Hz, while maintaining entering water temperature to the indoor heat exchanger and the outdoor heat exchanger at 12℃ and 25℃, respectively. The slope of the COP with a charge amount is much steeper at undercharged conditions than that at overcharged conditions. For all compressor speed, the variation of the system according to a change of charge amount showed the similar trends. However, the degradation of the system COP at high speed of the compressor was lower than it at low speed for over charged conditions.