사무소 건물의 내부발열 수준별 열관류율이 공조부하에 미치는 영향
이정훈, 안승현, 이상엽 et al. · 대한설비공학회 2014년도 하계학술발표대회 · 2014
Recently the Government strengthen the Standards of walls and windows thermal performance to reduce the energy consumption. U-Value of domestic windows Standards strengthened 3.37W/m2ㆍK in 1987 to 1.5W/m²ㆍK in 2013. However, These reinforcement of the building envelope is come from misunderstanding about insulation, and it is not always ensure the energy saving in office buildings. In this study, the effect of the performance(U-value) of building envelope on heating and cooling load according to the level of internal heat gain in office building was analyzed by simulation method(EnergyPlus). The results showed that the cooling load is no longer decreased at a certain level of window U-value. The cooling load is increased when the U-value is under a certain level.
Cited by 0 works.