오염농도분포 해석에 의한 주방배기풍량 평가
배상환, 임호진, 홍천화 · 대한설비공학회 학술발표대회논문집 · 1998
This study aimed to predict the optimal exhaust air volume that make contaminants disperse within kitchen of air conditioned complex building as a examination of building equipment before construction. This research was performed on the premise that only CO, CO₂ are contaminants. Three dimensional enclosure for analysis included kitchen, living room, utility room in unit. When range hood, exhaust fans in kitchen were on during cooking, the concentration and velocity distribution were examined. Standard k-e model was applied and transport equation for concentration was solved using CO, CO₂ as species. The effect of exhaust air volume variation on contaminant dispersal was examined through spatial distribution analysis of CO 10 ppm iso surface as a indoor environment standard. The minimum exhaust air volume for kitchen by unit type was suggested as a construction guideline. The application of CFD to this building will be verified by field experiment after construction. Afterwards furture work will include a variety of contaminants in the concentration analysis of environment field.
Cited by 0 works.