공동주택 환기시스템의 환기 성능 향상을 위한 최적 급ㆍ배기구 위치에 관한 연구

김동석, 김창남, 김우재 et al. · 대한건축학회 학술발표대회 논문집 - 계획계 · 2005

The purpose of this study is to suggest the optimum ventilation strategies In terms of the position of supply-return vent slots in mechanical ventilation system of an apartment housing. This paper introduced the field test results and the local ventilation effectiveness calculated by verified CFD analysis. The ventilation effectiveness was affected by the location of the outlet. The properly located ventilation outlets would allow the well-distributed clean air and the effective use of ventilation. However, the misplaced interval of outlets may cause the short circuiting of the ventilated air or the use of unnecessary energy by improper ventilation. Thus, the proper interval of outlets needs to be defined for the optimization of ventilation efficiency in an apartment housing. In the study, the relationship between the location of outlets and the possibility of short circuiting phenomenon is investigated by using a CFD(Computational Fluid Dynamics) analysis. The optimum solution to guarantee the efficient mechanical ventilation has been presented in terms of the supply-return vent slots.