진동형 히트 파이프를 이용한 매스 콘크리트의 겨울철 수화열 제어 특성
양태진, 김정훈, 염치선 et al. · 설비공학논문집 · 2007
In process of reinforced concrete (RC) box structure, the heat of hydration may cause serious thermal cracking. This paper reports results of hydration heat control in mass concrete using the oscillating heat pipe. There were three RC box molds (1.2m×1.8m×2.4m) which were different from each other. One was not equipped with pulsating heat pipe. The others were equipped with pulsating heat pipe. All of them were cooled with natural air convection. The pulsating heat pipe was composed of 10 turns of serpentine type copper pipe whose outer and inner diameters were 4 and 2.8 ㎜ respectively. The working fluid was R-22 and charging ratio was 40% by volume. The temperature of the concrete core was approximately 55 ℃ in the winter without pulsating heat pipe. For a concrete with pulsating heat pipe, however, the temperature difference with the outdoor one reduced up to 12℃. The index figure of crack was varied from 0.75 to 1.38.