천장형 에어컨 토출각 변화가 실내 열쾌적성에 미치는 영향

이진형, 김유재, 박성관 et al. · 유체기계 연구개발 발표회 논문집 · 2006

This paper considered the effect of discharge angles of 4-way cassette A/C on the indoor thermal comfort in high ceiling environment. The heat transfer from outdoor is considered through the window, the entrance door, ceiling, floor, and walls. The numerical study is performed with the height of the room in which is 3.6 m higher than the height of common building (2.7m). Using a commercial code, FLUENT, the numerical study is performed with incompressible, unsteady, three-dimensional and turbulence conditions. The indoor thermal comfort is analyzed with various discharge angles, β=45°, 50°, 55° and 60°. The thermal comfort is evaluated by EDT (effective draft temperature) and ADPI (air diffusion performance index) at ASHRAE Standard.