실내유동패턴에 따른 급기구별 기여도 평가에 관한 연구
한화택, 신철용, 이인복 et al. · 대한설비공학회 동계학술발표회 논문집 · 2009
This paper investigates the age of air in a ventilated space with multiple supply inlets. The local mean age of air at a point from one supply inlet is different from those from the other supply inlets. It is the purpose of the present paper to evaluate the contributions of each supply inlet to an internal point, using LMA values from each inlet and/or steady state concentrations by each inlet. Transient concentration distributions are calculated with a step-up injection of tracer gas at each supply inlet, and at both inlets simultaneously. The steady state concentration with a continuous tracer injection at a supply inlet works as a weighting factor for the corresponding LMA in calculating the average overall LMA from multiple inlets.