시스템 에어컨의 냉매충전량에 따른 사이클 운전특성 및 냉매량 판독 프로그램 개발
태상진, 김훈모, 조금남 et al. · 대한설비공학회 동계학술발표회 논문집 · 2005
This study developed a program for detecting charged refrigerant amount in system air-conditioner. System air-conditioner is an air-conditioning system with multiple indoor units. Due to the complexity of the system, it is more difficult to detect the refrigerant amount charged in system air-conditioner than in a general single air-conditioner. Experiments were performed for 6 HP outdoor units with 3 indoor units in a psychrometric calorimeter. The experimental amount of charged refrigerant were ranged from 60% to 140% with 10% increasement. Fuzzy algorithm were emploeed for detecting the charged refrigerant amount in a system air-conditioner. The experimental data were used for curve fitting for general ranges for indoor and outdoor temperature conditions. membership function were determined for whole ranges of experimentally measured data and rulebase were defined for each amount of refrigerant charge. Developed program successfully predicted the measured data within 10% resolution range.