극세관 헬리컬 코일형 증발관내 압력손실 특성

서석기, 김정훈, 강정길 et al. · 대한설비공학회 학술발표대회논문집 · 1998

As the standards of living is improved, demands of refrigeration and air conditioning systems are increasing every year. Compact and high effectiveness of systems is required to cut down the installation space, cost of productions and expenditures. And one of solutions to make out this high efficiency heat exchanger is using the small diameter tubes. So that, this research shows possibilities of adoption with the experiment like as the pressure drop of R-22 in small diameter helical coiled evaporation tube; Di=1.00㎜, Do=2.2㎜, curvature diameter: 31, 34, 47(㎜), length of pitch: 7.5, 9.1, 13.8(㎜). Experiments were carried out with following test conditions: saturated pressure: 4.92 (㎏_f/㎠), mass velocity; 150~500(㎏/㎡s), heat flux : 1~3(㎾/㎡). The results were summerized as followings: 1. In helical coiled tube, there is a secondary flow, so pressure drop is changed by heat flux as much as mass velocity. 2. Pressure drop is the lowest in case that curvature diameter is 34㎜. 3. Ito's correlation for two-phase friction factor is to be suitable for small diameter helical coiled tube.