고발열 전자부품 냉각용 써모사이폰의 냉각특성에 관한 연구
김광수, 김원태, 송규섭 et al. · 설비공학논문집 · 1998
The experimental study is concerned with two-phase closed thermosyphons, (i.e., wickless heat pipes) for the cooling of high power electronic components in telecommunication system. The thermosyphon which can deal with a high heat flux of up to 4.9 W/㎠ is developed, and the cooling characteristics of thermosyphon is analyzed according to design parameters which are the types of and quantity of working fluid, number of pipes, wire insertion in pipe, inclination angle of thermosyphon, and cooling air velocity. Using water as working fluid is superior cooling performance compared to using acetone, and cooling performance is improved as the number of thermosyphon becomes larger, inserting wires in the pipes, and inclination of 30~60°.