알루미늄 그루브 히트파이프 성능개선을 위한 실험적 연구
정원복, 변윤식, 양권옥 et al. · 1999
The experimental study for performance improvement of aluminum/freon22 grooved heat pipe was carried out. Artery wick was used for performance improvement. The result of experiment was compared with screen covered grooved wick heat pipe. And also, performance test of grooved wick thermosyphon inserted straight wire in the center of grooved pipe was carried out. This result was compared with grooved wick thermosyphon. The operation limit of artery inserted grooved heat pipe was slightly extended, but thermal resistance of this heat pipe was twice as large as that of screen covered grooved heat pipe. In the case thermosyphon, the operation limit of grooved thermosyphon inserted straight wire in the center of grooved pipe was significantly extended. But thermal resistance was slightly increased. comparing with that of the groove thermosyphon.