수평형 지열교환기 성능의 경년변화
황광일, 우상우, 김중헌 et al. · 대한설비공학회 학술발표대회논문집 · 2006
The purpose of this study is on the performance evaluation of horizontally installed GHEX(Geothermal Heat EXchanger, HGHEX) which has been operated for 5 years successfully. Followings are the results. Firstly, in summer season, on Aug. 2000, 33℃ water was flowing out from HGHEX with continuous operating method, and 27~29℃ with interval operating method on Jul. 2005. But 2.5~3.0℃ temperature differences are gained from HGHEX. Secondly, in winter season, on Nov. 2000, 25℃ water was flowing out from HGHEX with continuous operating method, and 13~15℃ with interval operating method on Jan. 2006. But with each operating method, only 0.1℃ and 0.7℃ temperature differences are gained from HGHEX respectively. As the conclusion of this study, at the point of continuos operating method, seasonal balance of heating and cooling loads, and at the point of interval operating method, balance for geothermal restoring time respectively must be considered for better system performances.
Cited by 0 works.