垂直管내를 흘러내리는 液膜式吸收器의 吸收 및 熱傳達 特性 (第3報, 蒸發器의 冷凍能力과 吸收器의 暖房能力)

엄기찬, 柏木孝夫, 서정윤 · 설비공학논문집 · 1994

This paper deals with the correlation of absorption rate in absorber and evaporation rate in evaporator. The evaporator consists of a copper tube of 10㎜ dia, and 600㎜ long and chilled water flowing through the tube is fed by the chilled water circulator. The flowrate of LiBr-water solution in the absorber plays a significant role in determining the magnitude of the heat transfer rate from chilled water to refrigerant There exists a flowrate of solution which has a maximum value of heat transfer. It is interesting to note that the absorption rate of absorber increases with increasing the heat transfer rate of the evaporator. Also, absorption rate increases with evaportation rate, and the ratio(the former/the other) depends on the inlet temperature of LiBr-water solution in the absorber. The heating capacity in the absorber is higher than the refrigerating capacity in the evaporator.

Cited by 0 works.

Authors