비등온 급기 조건에서 열원이 존재하는 공간에서의 환기방법에 따른 온도 분포 특성 연구

김성규, 이현우, 황유진 et al. · 대한설비공학회 하계학술발표회 논문집 · 2010

The objective in this paper is to analyze the temperature distribution in a non-isothermal condition with mixing ventilation and displacement ventilation systems for indoor thermal fields. In this study, the temperature distribution is evaluated in a model chamber (5.71 m × 3.57 m × 2.63 m) using a supply fan and exhaust fan with duct as a function of supply and exhaust positions. Air flow rate is 3870 CMH in each fan into the model chamber and heat source is 15 ㎾. In case of mixing ventilation, the temperature distribution is identical in each height except the 2.35 m due to the high mixing effect. In case of displacement ventilation, on the other hand, the temperature distribution according to the height is clearly distinguishable due to the buoyancy effect. The mean temperature was same in each way of ventilation, but, the temperature distribution of displacement ventilation was better than that of mixing ventilation viewpoints of cooling around heat source.