초고층 공동주택 외기전담 시스템 기반 중앙 공급식 환기시스템의 적정 급기조건 설정

김민휘, 김진효, 권오현 et al. · 한국태양에너지학회 학술대회논문집 · 2009

The main thrust of this paper is to investigate acceptable supply air conditions of a dedicated outdoor air system (DOAS) for highrise apartment buildings. As for a typical 132-㎡ apartment unit, it was assumed that centralized DOAS-Ceiling Radiant Cooling Panel was installed. Transient behavior and control characteristics of each system were modeled numerically using a commercial equation solver program. The optimized dew point temperature of the DOAS was discussed on the basis of the ASHRAE standard 62.1-2007 and the current Korean ventilation standard for apartments. It was found that the optimized dew point temperature of the DOAS supply air accommodating total latent load of a space is 11-12℃ and the appropriate supply air temperature of the DOAS is 11-12℃ in cooling period and neutral temperature of 18-20℃ in intermediate period.

Cited by 0 works.