저속치환 공조시스템의 현장적용 시험 연구
이계철, 김동규, 김경구 et al. · 대한설비공학회 동계학술발표회 논문집 · 2001
The objective of this paper is to investigate the field performance of the low velocity displacement air-conditioning system. A field testing is carried on in the first floor room of a school. The temperature distributions in the room space and around the supply unit are measured and visualized through smoke, with variation of the supply air quantity and the internal heat input as a cooling load. It is shown that the temperature distribution is stratified along the height, with high temperature in the upper side and lower temperature in the lower side. The cold supply air spreads along the bottom floor like a blanket and moves upward near the heat sources by natural convection. The contaminated air is displaced by the fresh air moves up along with the convection flow, resulting in fresh lower zone and contaminated upper zone with transition layer.
Cited by 0 works.