The Abstract: The method of determination of basic and vortex losses in the windings of the power transformer by the action of geoinduced currents of geomagnetic storms. It is shown that the effect of geoinduced current, high voltage winding of the power transformer TDTS-400000/220 more heat than low-voltage winding, so the most heated point belongs to HV winding power transformer. Are established permissible values of geoinduced currents in HV winding power transformer at various load factors TDTS-400000/220 power transformer, that limit the load capacity of the power transformer in geomagnetic storms.