전선의 단면분석을 통한 단락특성에 관한 연구

송길목, 최충석, 김윤회 et al. · 한국조명·전기설비학회 학술대회논문집 · 2005

For a fire cause judgement, this paper describes the short circuit characteristics of a electric wire through the cross section analysis under ac condition. The copper wires prepared for the experiment were 1.2mm, 1.6mm, and 2.0mm in diameter. Through the cross section analysis(CSA), it was confirmed that the dendrite structure grew at the angle of about 40° or 60° when the fusing current was applied to the wires. The larger the fusing current is, the more decreased the growth angle of the dendrite structure is. It was confirmed that the dendrite structure was arranged like the columnar structure. In this paper, the characteristics analysis of short circuit was carried out in the range of transient duration and the correlation constant k was investigated by measuring the short circuit duration and the fusing current.

Cited by 0 works.