열-전ㆍ자계 연성해석을 이용한 초고압 모선부의 온도상승 해석
안희섭, 윤정훈, 최종웅 et al. · 대한기계학회 춘추학술대회 · 2006
In development of High-voltage switchgear, proper thermal design becomes more and more important to provide safe function and reliability in spite of miniaturization and increasing performance demanded of modern devices. Due to the high complexity of heat generation and loss processes it is not easy to predict the thermal behavior of devices under various load conditions, i.e. usually numerous tests are required. To estimate the thermal performance of main bus, the 3D sequential coupled field thermal-magneto model was developed. The solution of the heat generation rate due to applied and eddy currents as well as skin and proximity effect is obtained using commercial electro-magnetic package. The solution for the fluid and temperature distribution is also obtained using commercial CFD package. The results of electromagnetic analysis are the inputs to the CFD analysis and vice versa until the steady state is reached. Temperature dependent material properties for both types of analyses are considered during the solution process. The predicted temperatures are quite well agreed with the experiments.