탄소블록과 동봉의 접지성능 비교 분석
서재석, 이정윤, 진창환 et al. · 한국철도학회 학술발표대회논문집 · 2013
This paper describes an analysis on grounding performance for a carbon block and a cooper rod. Two types of grounding systems buried at a depth of 0.8 [m] were compared; a three linked copperelectrodes of equilateral triangles with 1 [m] spacing and a carbon-electrode. The ground impedances were measured using the fall-of-potential method specified in IEEE Std. 81.2 and were calculated as the ratio of the peak potential rise to the peak injection current at same time. Applied current to the grounding system was a step pulse with a rising time of 500 [ns], a standard lightning impulse of 8/20 [μs] and a square waveform pulse of 1 [kHz]. We carried out a periodic measurement for seven months. Ground impedance for both increased with ages. Also, ground impedance of the three linked copper-electrodes was higher than that of carbon block to the 8/20 [μs] impulse and the square waveform pulse source.