열원온도의 변화에 따른 하수열원 열펌프 시스템 성능 특성의 실험적 고찰
이철민, 최영돈, 김용찬 · 대한설비공학회 학술발표대회논문집 · 2001
Performance of the water heat source heat pump system is mainly dependent upon the heat source and supply water temperatures. In the present study, COP of the heat pump system was measured with variation of the heat source temperature from 7 to 15℃, and supply water temperature from 30 to 40℃. COP of the heat pump system increases with the increase of heat source temperature while drops with the increase of supply water temperature. The variation of supply water temperature influences COP more than that of heat source temperature. Sewage water temperature varies from 5 to 15℃ according to the variation of environmental conditions. From this experimental investigation, it was found that COP of the sewage water heat source-heat pump system can maintain above 3.0 even in the winter season. However, water temperature of river drops to 2~3 ℃ in winter. So that COP of the heat pump system may drop below 3.0 in the winter season. Therefore in order to use the river water as the heat source of heat pump system, more study to increase the COP of the system should be performed.