병원 건물에 적용된 하이브리드 지열 히트펌프 시스템의 성능 분석

손병후, 이두영, 최재호 et al. · 대한설비공학회 동계학술발표회 논문집 · 2014

A hybrid geothermal heat pump(HGHP) system can decrease the first cost of geothermal heat pump systems by using conventional technology(such as a cooling tower or a boiler) to meet a portion of the peak cooling or heating load. This paper presents the experimental results of the performance of HGHP system using a cooling tower installed in hospital building. In order to demonstrate the performance of the hybrid approach, we installed the monitoring equipments including sensors for measuring temperature and power consumption and measured operation parameters from October 15, 2013 to current. The results showed that the entering source temperature of brine returning from the ground heat exchanger was in a range of the design target temperature. The ground heat exchanger rejected heat of 650.7 MWh to the ground. In addition, the GHP system extracted heat of 781.2 MWh from the building. Consequently, the average cooling seasonal performance factor (SPFc) of the overall system was evaluated to be 4.24 during the measurement period of cooling season.