난방운전 조건에서 히트펌프 칠러의 성능특성

박경만, 엄유식, 이상재 et al. · 대한설비공학회 동계학술발표회 논문집 · 2009

In the present study, the performance characteristics of R-410A heat-pump chiller in heating mode are experimentally investigated to understand capacity and reliability at the standard, the defrost, the low temperature and the on-off cycle conditions. Heating capacity, water flow rate and COP of R-410A heat-pump chiller are 11.4㎾, 33 l/min and 2.94, respectively. Heating capacity at low temperature condition decreases as the outside temperature decreases. From defrost and on-off cycle conditions, it is confirmed the reliability of R-410A heat-pump chiller.

Cited by 0 works.