해수열원 스크류 히트펌프의 연간 난방운전 성능 시뮬레이션
백영진, 김민성, 장기창 et al. · 한국태양에너지학회 춘계학술발표회 논문집 · 2012
In this study, in order to utilize the seawater as a heat source at Gangneung city near the East Sea in Korea, an annual heating performance of a screw heat pump was simulated. For a simulation, the maximum heating capacity of heat pump was assumed at 3.5 MW. An ambient temperature at Gangneung city was calculated from the TMY2 weather data, while the seawater temperature was calculated from the regression equation based on the measurement by the National Fisheries Research and Development Institute of Korea. The heating load was assumed linearly dependent on the ambient temperature, while the maximum heating load was assumed to appear when the ambient temperature is below -2.4 °C, which is the temperature of TAC 2.5% for heating at Gangneung city. A heat pump performance at full-load was calculated from the regression equation, which involves refrigerants evaporating and condensing temperatures, based on a commercial screw compressor performance map. A heating supply temperature which determines refrigerants condensing temperature was assumed linearly dependent on the heating load. A performance degradation due to the part-load operation of heat pump was also considered. Simulation results show that an annual heating coefficient of performance (COPh) of a seawater-source screw heat pump is approximately 2.8 and that it is necessary to improve part-load performance to increase an annual performance of the heat pump.