열교환기 내장형 어큐뮬레이터가 냉동시스템의 성능에 미치는 영향에 관한 연구
강훈, 최광민, 박차식 et al. · 대한설비공학회 동계학술발표회 논문집 · 2006
An AHX (Accumulator Heat eXchanger) consists of a commercial accumulator and an inner heat exchanger located inside of the accumulator. The AHX is used in multi air-conditioners to assure that liquid-phase refrigerant enters into the expansion device. This purpose is achieved by heat transfer between the refrigerant leaving the evaporator and the refrigerant leaving the condenser. In this study, the effects of AHX on the performance of a refrigeration system using R-22 were measured and the test results were analyzed. The operating characteristics of the refrigeration system with the AHX are considerably different from those without the AHX. Therefore, it is required to determine optimum refrigerant charge and optimum operating conditions when the AHX is used in the refrigeration system having a constant flow-area expansion device such as capillary tube.