열제어/화재안전 시험설비 운용에 따른 압력 및 온도 제어 특성 분석
고주용, 옥호남 · 한국추진공학회 학술대회논문집 · 2014
Analysis was performed to check the design suitability of facility in controlling the pressure and temperature in accordance with the operation of thermal control and fire safety facility. Three cases are examined with the maximum flow rate of 6000 kg/hr, nominal flow rate of 3000 kg/hr and two lines of 3000 kg/hr respectively. As a result, the pressure can be controlled by current design in every case but the temperature can be controlled only in the case of nominal flow rate application. The heater capacity is not sufficient for the case of 6000 kg/hr. These calculations were done with adiabatic condition in heat transfer, so for the case of 6000 kg/hr, new calculation will be needed including heat transfer condition in the future.