개방형 각-관 열교환기를 사용한 자연열원 열펌프의 성능
유성연, 박동성, 장광일 · 대한기계학회 춘추학술대회 · 2006
Present day, lots of researches for using the unutilized energy are performed. The fouling is the main problem of using the natural heat source existing in river water, swage water, sea water and so on. Various engineering research have been carried out for fouling removal and prevention such as chemical cleaning and sponge ball. In this research, the open type shell and tube heat exchanger was proposed for fouling prevention and adopted to 5RT class natural heat source heat pump as a evaporator. The ordinary shell and tube heat pump was manufactured and tested for comparison to open type shell and tube heat pump. The result of performance test, the open type shell and tube heat pump has same characteristics as ordinary shell and tube heat pump against water flow rate of heat exchanger. The open type shell and tube heat pump needs more water flow rate to obtain equivalent performance of ordinary shell and tube heat pump and can be adopted to heat exchanger of natural heat source heat pump.