히트펌프 조건 시 냉각 평판에서의 착상 실험
윤신혁, 조금남, 조홍기 et al. · 대한기계학회 춘추학술대회 · 2009
The present study measured the frost thickness and frost mass on a flat plate to propose the correlation equations for the local and average frost thickness, frost density, and frost mass. Key parameters were the cooling surface temperature of the flat plate from 258.2 to 268.2 K, absolute humidity of air from 2.98 to 4.16 g/㎏ DA , air temperature from 273.5 to 280.2 K, and air velocity from 1.0 to 2.5 ㎧. Although the area of the plate is the same, local frost thickness was changed along the direction of the flat plate. Correlation equations for the local and average frost thickness and frost mass under the heat pump condition were proposed. The predicted values by the correlation equations under the freezer condition showed larger by the maximum of 30~50% than the predicted values by the present correlation equations under the heat pump condition. The proposed correlation equations might be partly applied to the freezer condition.