공조용 덕트의 누기 및 강도 성능에 관한 실험적 연구

이태원, 김용기, 박노광 et al. · 대한기계학회 춘추학술대회 · 2002

In recent years energy losses in the duct work of forced air distribution systems have come under intensive a matter of concern. Energy losses in the duct work are due mainly to air leakage. Air leakage rates in commercial building duct systems are generally difficult to measure accurately. However a synthesis of measurement from a set of light commercial buildings reported an average leakage rate of approximately 25% of the flow through the supply fan. This paper presented comparisons of various duct connection methods by performing the tests on the air leakage and the strength. 'CD duct work', which has cross-beading steel plate and double flange connection, shows the highest performance on leakage prevention and nearly the same depression strength as 'L shape steel flange connection'. It turned out to be possible for the CD duct work to be able to decrease its tnickness due to the higher performance of the air leakage, the depression and swelling strength than that of any other duct works.