Air-conditioners use a spirally coiled capillary tube as an expansion device to enhance compactness of the unit. However, most empirical correlations in open literature were developed for straight capillary tubes without considering coiled effects on the mass flow rate. The objectives of this study are to investigate the flow characteristics of coiled capillary tubes and to develop a generalized correlation for mass flow rate through coiled capillary tubes. The mass flow rates through the coiled capillary tubes and straight capillary tubes were measured by varying operating conditions and tube geometry. The condensing temperatures varied at 40.5, 47.5, and 54.5℃, and subcoolings altered at 3.5, 6.5, and 11.5℃. The mass flow rates of the coiled capillary tubes decreased by 5 to 16% compared with those of the straight capillary tubes at the same operating conditions. An empirical correlation was developed by introducing non-dimensional parameters for operating conditions and coiled geometry based on the present data and the open literature database for R22.