전자팽창밸브의 제어인자에 따른 공기조화기의 성능변화

박윤철, 정규하, 이재권 et al. · 대한설비공학회 학술발표대회논문집 · 2001

This study was conducted to find optimal control parameters out for an EEV to get a higher performance in an air conditioning system. The system used inverter driven DC compressor and R410a as working refrigerant. Experimental apparatus was consisted with an air-conditioner calorimeter and an experimental simulator which controls the system automatically through a computer. It is founded that temperature difference between evaporator inlet and outlet is the most effective control parameter for the optimum performance of the system. In addition, compressor discharge temperature divided by compressor operating frequency could be a another parameters for the EEV control.

Cited by 0 works.

Authors