빙축열시스템 운전 시뮬레이션

이경호, 이학주, 권성철 et al. · 1999

The paper describes a system simulation of partial ice storage system composed of encapsulated ice storage tank, a screw compressor chiller, a heat exchanger, and brine pumps. The control strategies considered in this study are chiller priority and storage priority. Chiller priority is a common control method whereby storage is only used to match the difference between the building load and the maximum cooling capacity of the chillers. Although this control tends to minimize the use of storage for off-design days, it is easy to implement. Storage priority strategies involve maximizing the use of storage during the on-peak electrical periods. The storage priority investigated in this study is termed constant discharging during cooling period to deplete fully the stored ice at the end of the cooling period. It is simulated with design day cooling load of 600 tons of peak load and off-design day cooling load and compared with the electric energy costs of the two control strategies for the same system size.

Cited by 0 works.